Fire Alarm Loop Load: engineer's guide
Every SLC loop has a device limit, a current limit, and a resistance limit. Miss any and the panel supervises fault.
Open the Fire Alarm Loop Load →
What this calculator does
The calculator sums per-device current and resistance around the loop and reports remaining capacity against the panel-specified limits.
Formulas used
- Loop current:
Iloop = Σ Idevice + Idriver - Loop resistance:
Rloop = Σ Lsegment × rper m
Variables
- Idevice = per-device standby current, typically 300 to 500 μA
- r = cable resistance per metre (loop = both cores)
Worked example
Scenario: 80 addressable devices at 350 μA, 1.5 mm² twisted pair loop 400 m end-to-end.
- Iloop = 80 × 0.00035 + 0.060 driver = 0.088 A — under typical 500 mA limit
- Loop resistance = 400 × 2 × 12 mΩ/m = 9.6 Ω — under typical 40 Ω limit
- Both within panel limits; loop is compliant
Common mistakes to avoid
- Counting per-device current on the driver limit only
- One-way length instead of loop-length
- Missing the T-tap resistance for spurs
- Using shielded cable resistance from cold table (heats up)
Frequently asked questions
Class A or Class B loop?
Class A returns to the panel and survives a single break. Class B is spur. Class A required for critical premises per NFPA 72 Ch. 12.
Maximum devices per loop?
Panel-specified — typically 99 to 250 addressable devices per SLC loop.
Standards and references
NFPA 72, EN 54-13, BS 5839-1
Related tools on this site
Open the calculator that pairs with this guide: Fire Alarm Loop Load.
Verification note
This guide is planning support only. Final design must be verified against the applicable project specification, authority requirements, manufacturer data, and the standards cited above. Consult a licensed engineer for construction-issue calculations.