Worked examples for cable sizing, breaker rating, transformer, generator, kVA, ampacity, and power factor checks.
Cable Sizing & Voltage Drop Planner
Sample inputs: load: 75; voltage: 400; phase: three; pf: 0.85; length: 95; material: copper
- Code / standard profile: GCC project planning
- Calculated load current: 127.36 A
- Selected cable ampacity estimate: 210.00 A
- Ampacity margin: 64.9 %
Use at least 50 mm² as a preliminary cable size under these simplified assumptions.
Run calculatorElectrical Load Schedule Builder
Sample inputs: lighting: 22; sockets: 35; hvac: 120; motors: 45; other: 18; demand: 75
- Connected load: 240.00 kW
- Demand load: 180.00 kW
- Demand kVA: 204.55 kVA
- kVA with spare capacity: 245.45 kVA
Use 245.45 kVA as the planning load after demand and spare capacity.
Run calculatorTransformer Sizing & Spare Capacity Calculator
Sample inputs: load: 620; demand: 80; pf: 0.9; future: 20; maxLoading: 80
- Demand load: 496.00 kW
- Base transformer load: 551.11 kVA
- Required kVA at loading target: 826.67 kVA
- Recommended standard transformer: 1,000 kVA
Select approximately 1,000 kVA transformer capacity for the entered load and spare strategy.
Run calculatorGenerator Sizing & Starting Load Planner
Sample inputs: running: 180; pf: 0.8; motor: 45; startFactor: 2.5; diversity: 90; spare: 15
- Running diversified load: 202.50 kVA
- Starting allowance: 84.38 kVA
- Peak kVA with spare: 329.91 kVA
- Recommended generator size: 400 kVA
Plan around a 400 kVA generator before manufacturer step-load and voltage-dip verification.
Run calculatorPower Factor Correction & Payback Calculator
Sample inputs: kw: 350; currentPf: 0.72; targetPf: 0.95; voltage: 400; monthlySaving: 2600; costPerKvar: 180
- Required capacitor size: 222.31 kVAR
- kVA before correction: 486.11 kVA
- kVA after correction: 368.42 kVA
- Transformer relief: 117.69 kVA
Install approximately 222.31 kVAR capacitor capacity to move from 0.72 PF to 0.95 PF.
Run calculatorConduit Fill Calculator
Sample inputs: conduitArea: 860; cableArea: 95; quantity: 3; fillLimit: 40; codeProfile: gcc
- Code / standard profile: GCC project planning
- Total conductor area: 285 mm²
- Conduit fill: 33.1 %
- Entered fill limit: 40 %
Fill is within the entered 40 % limit.
Run calculatorShort Circuit Current Calculator
Sample inputs: kva: 1000; voltage: 400; impedance: 6; motorContribution: 10
- Transformer full-load current: 1,443 A
- Transformer fault current: 24.06 kA
- With motor contribution: 26.46 kA
- Impedance used: 6.00 %
Preliminary available fault current is about 26.46 kA at the transformer secondary.
Run calculatorLighting Lux Calculator
Sample inputs: area: 120; lux: 500; lumens: 4000; uf: 60; mf: 80
- Target luminous flux at workplane: 60,000 lm
- Adjusted required lumens: 125,000 lm
- Recommended luminaire count: 32 fixtures
- Installed lumen density: 1,042 lm/m²
Plan approximately 32 fixtures fixtures at 4,000 lm each before photometric verification.
Run calculatorBreaker Size Calculator
Sample inputs: kw: 45; voltage: 400; phase: 3; pf: 0.9; margin: 25; codeProfile: gcc
- Code / standard profile: GCC project planning
- Load current: 72.2 A
- Design current with margin: 90.2 A
- Recommended breaker rating: 100 A
Use approximately a 100 A breaker before checking cable ampacity, trip curve, and fault rating.
Run calculatorkVA to Amps Calculator
Sample inputs: kva: 100; voltage: 400; phase: 3
- Apparent power: 100.00 kVA
- Calculated current: 144.3 A
- Phase: Three phase
- Voltage used: 400 V
100.00 kVA equals about 144.3 A at 400 V three phase.
Run calculatorAmpacity Derating Calculator
Sample inputs: baseAmpacity: 150; temperatureFactor: 91; groupingFactor: 80; installationFactor: 95; loadCurrent: 95; codeProfile: gcc
- Code / standard profile: GCC project planning
- Base ampacity: 150.0 A
- Combined derating factor: 69.2 %
- Derated ampacity: 103.7 A
Derated ampacity is above the entered load current.
Run calculatorMEP Unit Converter
Sample inputs: value: 1200; conversion: cfm-lps
- Input value: 1,200.00
- Converted value: 566.336 L/s
- Conversion factor: 1 CFM = 0.471947 L/s
1,200.00 converts to 566.336 L/s.
Run calculator