Fire Alarm Battery Backup Calculator
Sample inputs: standbyCurrent: 1.8; alarmCurrent: 5.5; standbyHours: 24; alarmMinutes: 30; derating: 80; spare: 20
- Standby battery demand: 43.20 Ah
- Alarm battery demand: 2.75 Ah
- Raw required capacity: 45.95 Ah
- Adjusted required capacity: 68.93 Ah
Use at least 75 Ah battery capacity based on the entered standby, alarm, derating, and spare values.
Run calculatorFire Alarm Loop Load Calculator
Sample inputs: detectors: 82; modules: 18; sounders: 12; detectorMa: 0.35; moduleMa: 0.6; sounderMa: 4.5
- Total addressable devices: 112 devices
- Estimated loop current: 93.50 mA
- Loop current usage: 18.7 %
- Address usage: 44.8 %
The loop is at 18.7 % current usage and 44.8 % address usage under the entered assumptions.
Run calculatorFire Alarm DIP Switch Calculator
Sample inputs: fireSystem: zeta; address: 37
- Selected system profile: ZETA
- Device address shown: 37
- Switch count: 8 switches
- Binary value: 00100101
For ZETA, set S1 ON (1), S3 ON (4), S6 ON (32) for address 37. Verify the device manual before site programming or commissioning.
Run calculatorCCTV Storage Calculator
Sample inputs: cameras: 64; bitrate: 4; days: 30; hours: 24; raid: 15; spare: 20
- Raw recording storage: 82.94 TB
- RAID/formatting allowance: 12.44 TB
- Spare storage allowance: 16.59 TB
- Recommended usable storage: 111.97 TB
Plan approximately 111.97 TB usable storage for the entered retention period.
Run calculatorData Rack Power & UPS Calculator
Sample inputs: equipment: 1800; poe: 950; network: 350; spare: 25; runtime: 60; upsPf: 0.9
- Total rack load with spare: 3,875 W
- Required UPS capacity: 4.31 kVA
- Recommended UPS size: 5 kVA
- Estimated heat output: 13,222 BTU/h
Use around 5 kVA UPS capacity before selecting actual battery configuration and runtime package.
Run calculatorAccess Control Door Hardware Planner
Sample inputs: doors: 11; readersPerDoor: 2; controllerCapacity: 4; lockWatt: 6; voltage: 12; backup: 4
- Controllers required: 3 controllers
- Readers required: 22 readers
- REX devices: 11 devices
- Door contacts: 11 contacts
Plan 3 controller(s), 22 reader(s), and at least 6.60 A PSU capacity for the entered door hardware.
Run calculator