Cooling Load Estimator
Sample inputs: area: 450; occupants: 55; lighting: 12; equipment: 18; ventilation: 10; envelope: 85
- Envelope load: 38.25 kW
- Lighting load: 5.40 kW
- People + ventilation load: 13.79 kW
- Subtotal before latent/margin: 75.44 kW
Use approximately 27.13 TR as a preliminary cooling capacity before detailed heat-load verification.
Run calculatorDuct Sizing & Velocity Checker
Sample inputs: airflow: 2400; width: 600; height: 350; maxVelocity: 7; frictionClass: 1.2; codeProfile: gcc
- Airflow: 1.133 m³/s
- Duct area: 0.210 m²
- Calculated velocity: 5.39 m/s
- Equivalent round diameter: 496 mm
The selected duct is within the entered velocity target of 7.00 m/s.
Run calculatorAirflow & CFM Calculator
Sample inputs: area: 120; height: 3.2; ach: 8; people: 25; cfmPerson: 20; tons: 12
- Room volume: 384.00 m³
- ACH-based airflow: 1,808 CFM
- People ventilation airflow: 500 CFM
- Cooling-ton airflow: 4,800 CFM
Plan around 5,280 CFM based on the governing airflow method plus margin.
Run calculatorChilled Water Pipe Sizing Tool
Sample inputs: tons: 120; deltaT: 5.5; pipeId: 125; length: 90; maxVelocity: 2.4; margin: 10
- Cooling load: 422.04 kW
- Required flow: 72.59 m³/h
- Pipe velocity: 1.64 m/s
- Approximate friction head: 1.98 m
The selected pipe diameter is acceptable for preliminary velocity planning.
Run calculatorExhaust Fan Sizing Calculator
Sample inputs: length: 12; width: 8; height: 3.5; ach: 12; units: 4; cfmUnit: 75
- Room volume: 336.00 m³
- ACH-based exhaust: 2,373 CFM
- Fixture/equipment exhaust: 300 CFM
- Recommended fan capacity: 2,729 CFM
Select an exhaust fan around 2,729 CFM before checking external static pressure and acoustic criteria.
Run calculatorTR to CFM Calculator
Sample inputs: codeProfile: ashrae; tons: 18; cfmTon: 400; ventilation: 650; margin: 10
- Code / standard profile: ASHRAE planning
- Cooling airflow: 7,200 CFM
- Outdoor air allowance: 650 CFM
- Design margin: 10 %
Use approximately 8,635 CFM supply airflow for preliminary TR-to-CFM planning.
Run calculatorkW to BTU Calculator
Sample inputs: kw: 35
- Input capacity: 35.000 kW
- BTU per hour: 119,425 BTU/h
- Refrigeration tons: 9.952 TR
- kcal per hour: 30,115 kcal/h
35.000 kW is approximately 119,425 BTU/h or 9.952 TR.
Run calculatorKitchen Hood CFM Calculator
Sample inputs: codeProfile: ashrae; length: 2.4; depth: 1.1; captureVelocity: 90; exposureFactor: 115; margin: 10
- Code / standard profile: ASHRAE planning
- Hood plan area: 2.64 m2
- Hood plan area: 28.42 ft2
- Capture velocity used: 90 fpm
Plan approximately 3,235 CFM kitchen exhaust before manufacturer hood selection and balancing.
Run calculator