Water Demand Calculator
Sample inputs: occupants: 180; litersPerson: 135; fixturePeak: 420; diversity: 45; storageHours: 24
- Daily water demand: 24.30 m³/day
- Diversified peak flow: 189.00 L/min
- Peak flow: 3.15 L/s
- Storage volume for entered hours: 24.30 m³
Plan around 24.30 m³/day daily demand and 189.00 L/min diversified peak flow.
Run calculatorPump Head Calculator
Sample inputs: staticHead: 22; pressure: 2.5; flow: 18; pipeDiameter: 65; pipeLength: 85; fittings: 25
- Static head: 22.00 m
- Pressure head: 25.50 m
- Pipe velocity: 1.51 m/s
- Approximate friction head: 4.90 m
Select a pump around 18.00 m³/h at 57.64 m TDH, then verify against pump curves.
Run calculatorDrainage Pipe Sizing Assistant
Sample inputs: wc: 12; basins: 18; sinks: 4; floorDrains: 10; pipeDiameter: 110; slope: 1
- Estimated fixture units: 94 FU
- Planning pipe guidance: 110 mm
- Selected pipe diameter: 110 mm
- Entered slope: 1.00 %
The selected pipe diameter is acceptable for preliminary fixture-unit planning.
Run calculatorWater Tank Capacity Planner
Sample inputs: dailyDemand: 32; reserveDays: 1.5; fireReserve: 60; usable: 90; refillHours: 8; codeProfile: gcc
- Domestic reserve volume: 48.00 m³
- Separate fire reserve entered: 60.00 m³
- Net required usable volume: 108.00 m³
- Recommended gross tank volume: 120.00 m³
Provide approximately 120.00 m³ gross tank capacity for the entered domestic and fire reserve assumptions.
Run calculatorHot Water Demand Calculator
Sample inputs: occupants: 80; litersUser: 18; fixtureAllowance: 350; tempRise: 35; storageFactor: 70; recoveryHours: 2
- Peak hot water demand: 1,790.00 L
- Hot water per user applied: 18.00 L/user
- Recommended storage volume: 1,253.00 L
- Heating energy for storage: 50.99 kWh
Plan around 1,253.00 L storage and 25.50 kW heater recovery for the entered demand profile.
Run calculatorWater Pipe Pressure Drop Calculator
Sample inputs: flow: 12; diameter: 65; length: 80; fittings: 25; maxVelocity: 2; codeProfile: gcc
- Pipe velocity: 1.00 m/s
- Equivalent pipe length: 105.0 m
- Friction head loss: 2.08 m
- Pressure drop: 0.20 bar
Velocity is within the entered 2.00 m/s target.
Run calculatorDrainage Slope Calculator
Sample inputs: length: 18; slope: 1.5; startInvert: 100.25; minSlope: 1; codeProfile: gcc
- Pipe fall: 0.270 m
- Pipe fall: 270 mm
- End invert level: 99.980 m
- Gradient: 1:67
Over 18.00 m, a 1.50 % slope gives 270 mm fall.
Run calculatorPump Horsepower Calculator
Sample inputs: flow: 25; head: 45; efficiency: 68; motorMargin: 15
- Hydraulic power: 3.07 kW
- Shaft power: 4.51 kW
- Motor power with margin: 5.18 kW
- Motor horsepower: 6.95 HP
Plan around 5.18 kW motor power, or 6.95 HP, before pump-curve selection.
Run calculatorWater Pump NPSH Calculator
Sample inputs: atmosphericBar: 1.013; suctionHead: 2.5; vaporPressureBar: 0.023; suctionLoss: 0.8; npshr: 3.1; margin: 1
- Atmospheric head: 10.33 m
- Vapor pressure head: 0.23 m
- Available NPSH: 11.80 m
- Pump NPSHr: 3.10 m
NPSH margin meets the entered planning requirement.
Run calculator