Sample inputs, calculation outputs, interpretation notes, and report links for every active I Love MEP calculator.
Cooling Load Estimator
Sample inputs: area: 450; occupants: 55; lighting: 12; equipment: 18; ventilation: 10; envelope: 85
- Envelope load: 38.25 kW
- Lighting load: 5.40 kW
- People + ventilation load: 13.79 kW
- Subtotal before latent/margin: 75.44 kW
Use approximately 27.13 TR as a preliminary cooling capacity before detailed heat-load verification.
Run calculatorDuct Sizing & Velocity Checker
Sample inputs: airflow: 2400; width: 600; height: 350; maxVelocity: 7; frictionClass: 1.2; codeProfile: gcc
- Airflow: 1.133 m³/s
- Duct area: 0.210 m²
- Calculated velocity: 5.39 m/s
- Equivalent round diameter: 496 mm
The selected duct is within the entered velocity target of 7.00 m/s.
Run calculatorAirflow & CFM Calculator
Sample inputs: area: 120; height: 3.2; ach: 8; people: 25; cfmPerson: 20; tons: 12
- Room volume: 384.00 m³
- ACH-based airflow: 1,808 CFM
- People ventilation airflow: 500 CFM
- Cooling-ton airflow: 4,800 CFM
Plan around 5,280 CFM based on the governing airflow method plus margin.
Run calculatorChilled Water Pipe Sizing Tool
Sample inputs: tons: 120; deltaT: 5.5; pipeId: 125; length: 90; maxVelocity: 2.4; margin: 10
- Cooling load: 422.04 kW
- Required flow: 72.59 m³/h
- Pipe velocity: 1.64 m/s
- Approximate friction head: 1.98 m
The selected pipe diameter is acceptable for preliminary velocity planning.
Run calculatorExhaust Fan Sizing Calculator
Sample inputs: length: 12; width: 8; height: 3.5; ach: 12; units: 4; cfmUnit: 75
- Room volume: 336.00 m³
- ACH-based exhaust: 2,373 CFM
- Fixture/equipment exhaust: 300 CFM
- Recommended fan capacity: 2,729 CFM
Select an exhaust fan around 2,729 CFM before checking external static pressure and acoustic criteria.
Run calculatorSprinkler Density & Coverage Planner
Sample inputs: density: 8.1; designArea: 230; coverage: 12; hose: 950; duration: 60; margin: 10
- Estimated sprinkler count: 20 heads
- Sprinkler flow demand: 1,863 L/min
- Total demand with hose and margin: 3,094 L/min
- Required fire water volume: 278.49 m³
Plan around 3,094 L/min total flow and 278.49 m³ water volume for this preliminary scenario.
Run calculatorFire Pump Sizing Calculator
Sample inputs: sprinkler: 1850; hose: 950; hydrant: 0; elevation: 18; residual: 4.5; pipeLoss: 1.2
- Total pump flow: 3,080 L/min
- Total pump flow: 814 GPM
- Estimated pump head: 76.14 m
- Estimated pump pressure: 7.46 bar
Use approximately 3,080 L/min at 76.14 m head for preliminary fire pump planning.
Run calculatorFire Hose Reel / Hydrant Demand Tool
Sample inputs: reels: 4; reelFlow: 100; hydrants: 2; hydrantFlow: 500; simultaneous: 75; duration: 60
- Base connected fire flow: 1,400 L/min
- Simultaneous demand: 1,050 L/min
- Demand in GPM: 277 GPM
- Required water volume: 94.50 m³
Use 1,050 L/min as the preliminary simultaneous hose/hydrant demand.
Run calculatorFire Water Tank Capacity Calculator
Sample inputs: sprinkler: 1850; hose: 950; hydrant: 0; duration: 60; usable: 90; refill: 150
- Total fire demand: 2,800 L/min
- Gross demand volume: 252.00 m³
- Refill contribution: 13.50 m³
- Required usable storage: 238.50 m³
Provide approximately 265.00 m³ gross tank capacity based on entered usable volume and refill assumptions.
Run calculatorFM200 / Clean Agent Quantity Estimator
Sample inputs: length: 8; width: 6; height: 3.2; factor: 0.72; reserve: 10; cylinder: 45
- Protected room volume: 153.60 m³
- Base agent quantity: 110.59 kg
- Total with reserve: 121.65 kg
- Cylinder capacity entered: 45.00 kg
Plan approximately 121.65 kg of agent, or 3 cylinders based on the entered cylinder size.
Run calculatorCable Sizing & Voltage Drop Planner
Sample inputs: load: 75; voltage: 400; phase: three; pf: 0.85; length: 95; material: copper
- Code / standard profile: GCC project planning
- Calculated load current: 127.36 A
- Selected cable ampacity estimate: 210.00 A
- Ampacity margin: 64.9 %
Use at least 50 mm² as a preliminary cable size under these simplified assumptions.
Run calculatorElectrical Load Schedule Builder
Sample inputs: lighting: 22; sockets: 35; hvac: 120; motors: 45; other: 18; demand: 75
- Connected load: 240.00 kW
- Demand load: 180.00 kW
- Demand kVA: 204.55 kVA
- kVA with spare capacity: 245.45 kVA
Use 245.45 kVA as the planning load after demand and spare capacity.
Run calculatorTransformer Sizing & Spare Capacity Calculator
Sample inputs: load: 620; demand: 80; pf: 0.9; future: 20; maxLoading: 80
- Demand load: 496.00 kW
- Base transformer load: 551.11 kVA
- Required kVA at loading target: 826.67 kVA
- Recommended standard transformer: 1,000 kVA
Select approximately 1,000 kVA transformer capacity for the entered load and spare strategy.
Run calculatorGenerator Sizing & Starting Load Planner
Sample inputs: running: 180; pf: 0.8; motor: 45; startFactor: 2.5; diversity: 90; spare: 15
- Running diversified load: 202.50 kVA
- Starting allowance: 84.38 kVA
- Peak kVA with spare: 329.91 kVA
- Recommended generator size: 400 kVA
Plan around a 400 kVA generator before manufacturer step-load and voltage-dip verification.
Run calculatorPower Factor Correction & Payback Calculator
Sample inputs: kw: 350; currentPf: 0.72; targetPf: 0.95; voltage: 400; monthlySaving: 2600; costPerKvar: 180
- Required capacitor size: 222.31 kVAR
- kVA before correction: 486.11 kVA
- kVA after correction: 368.42 kVA
- Transformer relief: 117.69 kVA
Install approximately 222.31 kVAR capacitor capacity to move from 0.72 PF to 0.95 PF.
Run calculatorFire Alarm Battery Backup Calculator
Sample inputs: standbyCurrent: 1.8; alarmCurrent: 5.5; standbyHours: 24; alarmMinutes: 30; derating: 80; spare: 20
- Standby battery demand: 43.20 Ah
- Alarm battery demand: 2.75 Ah
- Raw required capacity: 45.95 Ah
- Adjusted required capacity: 68.93 Ah
Use at least 75 Ah battery capacity based on the entered standby, alarm, derating, and spare values.
Run calculatorFire Alarm Loop Load Calculator
Sample inputs: detectors: 82; modules: 18; sounders: 12; detectorMa: 0.35; moduleMa: 0.6; sounderMa: 4.5
- Total addressable devices: 112 devices
- Estimated loop current: 93.50 mA
- Loop current usage: 18.7 %
- Address usage: 44.8 %
The loop is at 18.7 % current usage and 44.8 % address usage under the entered assumptions.
Run calculatorFire Alarm DIP Switch Calculator
Sample inputs: fireSystem: zeta; address: 37
- Selected system profile: ZETA
- Device address shown: 37
- Switch count: 8 switches
- Binary value: 00100101
For ZETA, set S1 ON (1), S3 ON (4), S6 ON (32) for address 37. Verify the device manual before site programming or commissioning.
Run calculatorCCTV Storage Calculator
Sample inputs: cameras: 64; bitrate: 4; days: 30; hours: 24; raid: 15; spare: 20
- Raw recording storage: 82.94 TB
- RAID/formatting allowance: 12.44 TB
- Spare storage allowance: 16.59 TB
- Recommended usable storage: 111.97 TB
Plan approximately 111.97 TB usable storage for the entered retention period.
Run calculatorData Rack Power & UPS Calculator
Sample inputs: equipment: 1800; poe: 950; network: 350; spare: 25; runtime: 60; upsPf: 0.9
- Total rack load with spare: 3,875 W
- Required UPS capacity: 4.31 kVA
- Recommended UPS size: 5 kVA
- Estimated heat output: 13,222 BTU/h
Use around 5 kVA UPS capacity before selecting actual battery configuration and runtime package.
Run calculatorAccess Control Door Hardware Planner
Sample inputs: doors: 11; readersPerDoor: 2; controllerCapacity: 4; lockWatt: 6; voltage: 12; backup: 4
- Controllers required: 3 controllers
- Readers required: 22 readers
- REX devices: 11 devices
- Door contacts: 11 contacts
Plan 3 controller(s), 22 reader(s), and at least 6.60 A PSU capacity for the entered door hardware.
Run calculatorWater Demand Calculator
Sample inputs: occupants: 180; litersPerson: 135; fixturePeak: 420; diversity: 45; storageHours: 24
- Daily water demand: 24.30 m³/day
- Diversified peak flow: 189.00 L/min
- Peak flow: 3.15 L/s
- Storage volume for entered hours: 24.30 m³
Plan around 24.30 m³/day daily demand and 189.00 L/min diversified peak flow.
Run calculatorPump Head Calculator
Sample inputs: staticHead: 22; pressure: 2.5; flow: 18; pipeDiameter: 65; pipeLength: 85; fittings: 25
- Static head: 22.00 m
- Pressure head: 25.50 m
- Pipe velocity: 1.51 m/s
- Approximate friction head: 4.90 m
Select a pump around 18.00 m³/h at 57.64 m TDH, then verify against pump curves.
Run calculatorDrainage Pipe Sizing Assistant
Sample inputs: wc: 12; basins: 18; sinks: 4; floorDrains: 10; pipeDiameter: 110; slope: 1
- Estimated fixture units: 94 FU
- Planning pipe guidance: 110 mm
- Selected pipe diameter: 110 mm
- Entered slope: 1.00 %
The selected pipe diameter is acceptable for preliminary fixture-unit planning.
Run calculatorWater Tank Capacity Planner
Sample inputs: dailyDemand: 32; reserveDays: 1.5; fireReserve: 60; usable: 90; refillHours: 8; codeProfile: gcc
- Domestic reserve volume: 48.00 m³
- Separate fire reserve entered: 60.00 m³
- Net required usable volume: 108.00 m³
- Recommended gross tank volume: 120.00 m³
Provide approximately 120.00 m³ gross tank capacity for the entered domestic and fire reserve assumptions.
Run calculatorHot Water Demand Calculator
Sample inputs: occupants: 80; litersUser: 18; fixtureAllowance: 350; tempRise: 35; storageFactor: 70; recoveryHours: 2
- Peak hot water demand: 1,790.00 L
- Hot water per user applied: 18.00 L/user
- Recommended storage volume: 1,253.00 L
- Heating energy for storage: 50.99 kWh
Plan around 1,253.00 L storage and 25.50 kW heater recovery for the entered demand profile.
Run calculatorConduit Fill Calculator
Sample inputs: conduitArea: 860; cableArea: 95; quantity: 3; fillLimit: 40; codeProfile: gcc
- Code / standard profile: GCC project planning
- Total conductor area: 285 mm²
- Conduit fill: 33.1 %
- Entered fill limit: 40 %
Fill is within the entered 40 % limit.
Run calculatorShort Circuit Current Calculator
Sample inputs: kva: 1000; voltage: 400; impedance: 6; motorContribution: 10
- Transformer full-load current: 1,443 A
- Transformer fault current: 24.06 kA
- With motor contribution: 26.46 kA
- Impedance used: 6.00 %
Preliminary available fault current is about 26.46 kA at the transformer secondary.
Run calculatorLighting Lux Calculator
Sample inputs: area: 120; lux: 500; lumens: 4000; uf: 60; mf: 80
- Target luminous flux at workplane: 60,000 lm
- Adjusted required lumens: 125,000 lm
- Recommended luminaire count: 32 fixtures
- Installed lumen density: 1,042 lm/m²
Plan approximately 32 fixtures fixtures at 4,000 lm each before photometric verification.
Run calculatorWater Pipe Pressure Drop Calculator
Sample inputs: flow: 12; diameter: 65; length: 80; fittings: 25; maxVelocity: 2; codeProfile: gcc
- Pipe velocity: 1.00 m/s
- Equivalent pipe length: 105.0 m
- Friction head loss: 2.08 m
- Pressure drop: 0.20 bar
Velocity is within the entered 2.00 m/s target.
Run calculatorBreaker Size Calculator
Sample inputs: kw: 45; voltage: 400; phase: 3; pf: 0.9; margin: 25; codeProfile: gcc
- Code / standard profile: GCC project planning
- Load current: 72.2 A
- Design current with margin: 90.2 A
- Recommended breaker rating: 100 A
Use approximately a 100 A breaker before checking cable ampacity, trip curve, and fault rating.
Run calculatorkVA to Amps Calculator
Sample inputs: kva: 100; voltage: 400; phase: 3
- Apparent power: 100.00 kVA
- Calculated current: 144.3 A
- Phase: Three phase
- Voltage used: 400 V
100.00 kVA equals about 144.3 A at 400 V three phase.
Run calculatorAmpacity Derating Calculator
Sample inputs: baseAmpacity: 150; temperatureFactor: 91; groupingFactor: 80; installationFactor: 95; loadCurrent: 95; codeProfile: gcc
- Code / standard profile: GCC project planning
- Base ampacity: 150.0 A
- Combined derating factor: 69.2 %
- Derated ampacity: 103.7 A
Derated ampacity is above the entered load current.
Run calculatorDrainage Slope Calculator
Sample inputs: length: 18; slope: 1.5; startInvert: 100.25; minSlope: 1; codeProfile: gcc
- Pipe fall: 0.270 m
- Pipe fall: 270 mm
- End invert level: 99.980 m
- Gradient: 1:67
Over 18.00 m, a 1.50 % slope gives 270 mm fall.
Run calculatorPump Horsepower Calculator
Sample inputs: flow: 25; head: 45; efficiency: 68; motorMargin: 15
- Hydraulic power: 3.07 kW
- Shaft power: 4.51 kW
- Motor power with margin: 5.18 kW
- Motor horsepower: 6.95 HP
Plan around 5.18 kW motor power, or 6.95 HP, before pump-curve selection.
Run calculatorTR to CFM Calculator
Sample inputs: codeProfile: ashrae; tons: 18; cfmTon: 400; ventilation: 650; margin: 10
- Code / standard profile: ASHRAE planning
- Cooling airflow: 7,200 CFM
- Outdoor air allowance: 650 CFM
- Design margin: 10 %
Use approximately 8,635 CFM supply airflow for preliminary TR-to-CFM planning.
Run calculatorMEP Unit Converter
Sample inputs: value: 1200; conversion: cfm-lps
- Input value: 1,200.00
- Converted value: 566.336 L/s
- Conversion factor: 1 CFM = 0.471947 L/s
1,200.00 converts to 566.336 L/s.
Run calculatorkW to BTU Calculator
Sample inputs: kw: 35
- Input capacity: 35.000 kW
- BTU per hour: 119,425 BTU/h
- Refrigeration tons: 9.952 TR
- kcal per hour: 30,115 kcal/h
35.000 kW is approximately 119,425 BTU/h or 9.952 TR.
Run calculatorKitchen Hood CFM Calculator
Sample inputs: codeProfile: ashrae; length: 2.4; depth: 1.1; captureVelocity: 90; exposureFactor: 115; margin: 10
- Code / standard profile: ASHRAE planning
- Hood plan area: 2.64 m2
- Hood plan area: 28.42 ft2
- Capture velocity used: 90 fpm
Plan approximately 3,235 CFM kitchen exhaust before manufacturer hood selection and balancing.
Run calculatorWater Pump NPSH Calculator
Sample inputs: atmosphericBar: 1.013; suctionHead: 2.5; vaporPressureBar: 0.023; suctionLoss: 0.8; npshr: 3.1; margin: 1
- Atmospheric head: 10.33 m
- Vapor pressure head: 0.23 m
- Available NPSH: 11.80 m
- Pump NPSHr: 3.10 m
NPSH margin meets the entered planning requirement.
Run calculator